TAC INET MR-VAV-X1X2 VAV Controllers.EN.pdf

(833 KB) Pobierz
TAC I/NET M R-VAV-X X Series
Application Speciic
MicroRegulator
TAC’s MR-VAV-XX Series Application Speciic
MicroRegulator TM has an extensive range of pre-engineered
VAV control sequences which, combined with a fully
integrated airlow transducer, makes it a low “Total Installed
Cost” solution for most VAV terminal unit control applications
requiring an external actuator. An intelligent I/STAT TM
interface for independent local control and an interface to a
TAC I/NET TM Distributed Control System are
standard options.
946676750.174.png 946676750.185.png 946676750.196.png 946676750.207.png 946676750.001.png 946676750.012.png 946676750.023.png 946676750.034.png 946676750.045.png 946676750.056.png 946676750.067.png 946676750.078.png 946676750.089.png 946676750.100.png 946676750.111.png 946676750.122.png 946676750.133.png 946676750.138.png
 
02
M R-VAV-X X Series
Application Speciic MicroRegulator
Features
Operation
The MR-VAV-XX is the complimentary VAV
controller to the MR-VAV-AX except it has no
integral damper actuator. It has been designed for
applications requiring connection to a box-supplied
damper actuator. This controller has also been
designed to minimize the total installation, setup,
coniguration and commissioning costs typically
associated with VAV controllers.
PRoDuCT AT A GLANCE
MR-VAV-XX Features
Fully Integrated Airflow Transducer(s) and
Controller in a single DIN rail mountable package
Standalone and Networked Applications
Extensive VAV Control Sequences:
– Single/Dual Duct
– Three Stage Heating, Multiple Modes
– Series/Parallel Fan
– Local/Remote occupancy override
– Local/Remote Central Plant Heat or Morning
Warm-up Control
– Local/Remote Shut Down override (fire,
failure, etc.)
– Indoor Air Quality Airflow Setpoint override
– Demand Control Setpoint override
– Minimum and Maximum Airflow Parameters for
both Heating and Cooling
Complete “out-of-the-Box” Installation,
Configuration and Commissioning
– DIP Switch Configuration and Network
Addressing with Local/Remote override
– Automated Calibration of Airflow and
Temperature Sensors
– Autoconfiguration of Heating Stages
– “Prove It” function for Performance
Verification
– Automatic Database Distribution for
Networked Configurations
– Default Parameter Values
– Configuration and Commissioning from I/
STAT, M/STAT or PC
– Auto rescaling of velocity transducer(s) in low
flow application
– Self-Test Diagnostics
Installation costs have been reduced by totally
integrating the airlow transducer(s) and controller
into a single, plenum rated package that can be
mounted on a DIN rail.
Setup costs have been reduced by the provision of
DIP switches that can be set during installation and
before power is applied. Default parameters will
allow the controller to run immediately from startup
based on these switch settings.
The MR-VAV-XX is also supplied with an
extensive range of pre-engineered and tested
control sequences and therefore, no application
programming is required.
All coniguration parameters are pre-installed with
the most typical default values. However, they
can be overwritten either by a connected I/STAT,
an M/STAT (a portable I/STAT) or the Operator
Station PC. Heating stage setpoints, proportional
bands and delays are automatically calculated
and set in the controller based on the controller
setup selection.
Commissioning costs have been reduced
by the use of several automated processes.
Airlow conversion parameters are automatically
calculated once the box duct diameter and the
manufacturer’s K-factor are entered. By measuring
and entering the low and high airlow values for the
box, automatic calibration of the installed airlow
transducer is then performed.
Automated calibration of the temperature sensor
is also initiated once a measured value is entered
into the controller. A “Prove It” function allows a
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-INET-VAV-X1-X2-A4.BU.N.EN.5.2006.0.00.CC
946676750.139.png 946676750.140.png
03
M R-VAV-X X Series
Application Speciic MicroRegulator
Features
connected Application Speciic MicroRegulators.
This database can also include a unique eight-
character name for each controller as part of each
point descriptor.
In a standalone coniguration, the controller
provides auxiliary inputs for VAV Shutdown (e.g.
ire alarm), Occupancy Override (e.g. Timer, Push-
button or Occupancy Sensor), and Central Plant
Heat or Morning Warm-Up Override (e.g. contacts
from a central plant).
PRoDuCT AT A GLANCE
(CoNTINuED)
I/STAT and M/STAT Support Standard
– Local Display – 3 Digit & Decimal
– Local Point Control – Analog or Digital
– Local override & Setpoint Adjustment
– Service Mode for Commissioning and
Calibration
– user-Defined Passwords
Slide/STAT Support Standard
– Slide Setpoint override
– occupancy override
– Integral Port for M/STAT Connection
Inputs
– Airflow Transducer (one or two)
– Thermistor or Discrete (four)
Low Voltage Triac outputs for
– Primary and Secondary Damper Actuators
– Series/Parallel Fan Control
– First Stage Heater Control
(Two Position, Frequency Modulated, Pulse
Width Modulated or Floating Control Modes)
– Second Stage Heater Control
(Two Position Control only)
– Third Stage Heater Control
(Two Position Control only)
In a network environment, these signals can be
provided locally for the standalone mode or via
the network. If these inputs are not used for local
override signals, then they can be designated as
“free” and used for any auxiliary input condition
monitoring desired in a networked environment
(e.g. supply air temperature). This is also applicable
to any unused outputs. They can become available
for control applications resident in the MCI or I/
SITE LAN (e.g. lighting control).
A networked environment of MR-VAV-XX
controllers can provide an extensive range of global
interlocks. These include Demand Mode setpoint
override, Central Plant Heat/Morning Warm-up,
Smoke Control (purge and isolate), Indoor Air
Quality (IAQ) Minimum Airlow setpoint override,
Temperature Setpoint override and Occupancy
override.
Also, the current damper actuator position is
continuously calculated and available as an Analog
Output value that is a percentage of full damper
stroke. This eliminates the need for expensive
feedback potentiometers and analog voltage
controlled (0-10Vdc) damper actuators. Also,
this analog output point can be overridden either
manually from an operator station or automatically
via an application program in the MCI or I/SITE LAN
and the actuator driven to any desired absolute
position.
complete veriication of the control sequence from
an I/STAT or M/STAT. Once initiated, the space
temperature is placed in Test Mode and can be
“increased” or “decreased” by the buttons on the I/
STAT. As the temperature value is changed through
the control range, the I/STAT displays the airlow
value and the state of the fan and auxiliary heating.
This allows conirmation of the thermodynamic
process from end to end. Finally, in a networked
environment, the database for the MicroController
Interface or an I/SITE LAN can be automatically
generated by an upload of all the data in the
The controller can also provide an analog value of
the current controller loading as a percentage value
of full load, for both cooling and heating modes.
This value can be used in the networked system
to provide an accurate signal to the central plant
controllers of actual system load requirements.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-INET-VAV-X1-X2-A4.BU.N.EN.5.2006.0.00.CC
946676750.141.png 946676750.142.png
04
M R-VAV-X X Series
Application Speciic MicroRegulator
Features
MR-VAV-XX
Model
Number Description
Comments
Connections
7716
Process Control unit,
8 uI, 8 Do (Relay),
24Vac
Baseplate
Mounted,
accommodates
the RS-232
Communications
Expansion Board,
and/or one of the
Point I/o modules
listed below.
MR-VAV-X1
Application Speciic
MicroRegulator,
1 I/STAT Port, 1
Integrated Airlow
Transducer, 4
Thermistor or
Discrete Inputs, 6
Low Voltage Triac
outputs, 24Vac
External Actuator
required
MR-VAV-X2
Application Speciic
MicroRegulator,
1 I/STAT Port, 2
Integrated Airlow
Transducers, 4
Thermistor or
Discrete Inputs, 6
Low Voltage Triac
outputs, 24Vac
External Actuator
required
TCoN155
Application Speciic
MicroRegulator
Installation Guide
MR-VAV-X1
TCoN156
Application Speciic
MicroRegulator
Installation Sheet
MR-VAV-X2
TCoN149
Application Speciic
MicroRegulator
Pocket Guide
MR-VAV
TCoN164
MR-VAV-X2
Installation/
Reference Guide
TCoN165
MR-VAV-X2
Installation Sheet
TCoN166
MR-VAV-X2 Pocket
Guide
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-INET-VAV-X1-X2-A4.BU.N.EN.5.2006.0.00.CC
946676750.143.png 946676750.144.png 946676750.145.png 946676750.146.png 946676750.147.png 946676750.148.png 946676750.149.png 946676750.150.png 946676750.151.png 946676750.152.png 946676750.153.png 946676750.154.png 946676750.155.png 946676750.156.png 946676750.157.png 946676750.158.png 946676750.159.png 946676750.160.png 946676750.161.png 946676750.162.png 946676750.163.png 946676750.164.png 946676750.165.png 946676750.166.png 946676750.167.png 946676750.168.png 946676750.169.png 946676750.170.png 946676750.171.png 946676750.172.png 946676750.173.png 946676750.175.png 946676750.176.png 946676750.177.png 946676750.178.png 946676750.179.png 946676750.180.png 946676750.181.png 946676750.182.png 946676750.183.png 946676750.184.png 946676750.186.png 946676750.187.png 946676750.188.png 946676750.189.png 946676750.190.png 946676750.191.png 946676750.192.png 946676750.193.png 946676750.194.png 946676750.195.png 946676750.197.png 946676750.198.png 946676750.199.png 946676750.200.png 946676750.201.png 946676750.202.png 946676750.203.png 946676750.204.png 946676750.205.png 946676750.206.png 946676750.208.png 946676750.209.png 946676750.210.png 946676750.211.png 946676750.212.png 946676750.213.png 946676750.214.png 946676750.215.png 946676750.216.png 946676750.217.png 946676750.002.png 946676750.003.png 946676750.004.png 946676750.005.png 946676750.006.png 946676750.007.png 946676750.008.png 946676750.009.png 946676750.010.png 946676750.011.png 946676750.013.png 946676750.014.png 946676750.015.png 946676750.016.png 946676750.017.png 946676750.018.png 946676750.019.png 946676750.020.png 946676750.021.png 946676750.022.png 946676750.024.png 946676750.025.png 946676750.026.png 946676750.027.png 946676750.028.png 946676750.029.png 946676750.030.png 946676750.031.png 946676750.032.png 946676750.033.png 946676750.035.png 946676750.036.png 946676750.037.png 946676750.038.png 946676750.039.png 946676750.040.png 946676750.041.png 946676750.042.png 946676750.043.png 946676750.044.png 946676750.046.png 946676750.047.png 946676750.048.png 946676750.049.png 946676750.050.png 946676750.051.png 946676750.052.png 946676750.053.png 946676750.054.png 946676750.055.png 946676750.057.png 946676750.058.png 946676750.059.png 946676750.060.png 946676750.061.png 946676750.062.png 946676750.063.png 946676750.064.png 946676750.065.png 946676750.066.png 946676750.068.png 946676750.069.png 946676750.070.png 946676750.071.png 946676750.072.png 946676750.073.png 946676750.074.png 946676750.075.png 946676750.076.png 946676750.077.png 946676750.079.png 946676750.080.png 946676750.081.png 946676750.082.png 946676750.083.png 946676750.084.png 946676750.085.png 946676750.086.png 946676750.087.png 946676750.088.png 946676750.090.png 946676750.091.png 946676750.092.png 946676750.093.png 946676750.094.png 946676750.095.png 946676750.096.png 946676750.097.png 946676750.098.png 946676750.099.png 946676750.101.png 946676750.102.png 946676750.103.png 946676750.104.png 946676750.105.png 946676750.106.png 946676750.107.png 946676750.108.png 946676750.109.png 946676750.110.png 946676750.112.png 946676750.113.png 946676750.114.png 946676750.115.png 946676750.116.png 946676750.117.png 946676750.118.png 946676750.119.png 946676750.120.png 946676750.121.png 946676750.123.png 946676750.124.png 946676750.125.png 946676750.126.png 946676750.127.png 946676750.128.png 946676750.129.png 946676750.130.png 946676750.131.png 946676750.132.png 946676750.134.png 946676750.135.png 946676750.136.png
 
05
M R-VAV-X X Series
Application Speciic MicroRegulator
Speciications
Process Control unit
SOFTWARE
POINT CAPACITY:
20 resident points. Hardware (external)
points are a function of model selected,
and software (internal or indirect) points
activated. Indirect points are non-local
relections of any “global” point in the TAC I/
NET system.
INPUT/OUTPUT
SPACE SENSOR INPUT:
Supports I/STAT, Slide/STAT or
10K Ohm NTC Thermistor
(Dale 1M1002-C3)
Accuracy: 1°F (0.60°C)
Resolution: 0.32°F (0.18°C) @ 77°F (25°C)
INPUTS:
May be either thermistor or discrete contacts
per the following speciications.
ANALOG INPUTS:
10K Ohm NTC Thermistor
(Dale 1M1002-C3)
Accuracy: 1%
Resolution: 0.4% Span
A/D Digital Filtering: Median value ilter and
60 Hz notch ilter
Calibration Coeficients: Factory set in
NOVRAM, ield adjustable,
7 individual pairs.
DIGITAL INPUTS:
Dry contact input
Contact Excitation: 5V @ 0.5 mA
DISCRETE OUTPUTS:
Low Voltage Triac: 24Vac @ 0.5A max
(voltage sourcing), fused.
POINT SCAN INTERVAL:
1 – 255 seconds
VELOCITY PRESSURE INPUT:
Operating Range: 0.0 to 1.00 in. of W.C.
(0.0 to 250Pa)
Sensitivity: 0.0029˝ W.C. (0.73Pa) below
midscale and 0.0049˝ W.C. (1.10Pa) above
midscale.
Tubing Connections: Barb ittings for
0.170˝ (4.3 mm) I.D. FRPE polyethyl-
ene tubing or 0.25˝ O.D./0.125˝ I.D. (6.3
mm/3.2 mm) tygon tubing.
Tubing Length: 4 ft (1.2 m) maximum each
tube.
TERMINATIONS
TERMINAL BLOCKS:
Removable screw termina connectors
INDICATION
LEDs:
MR LAN activity (transmitting & receiving –
each channel), test mode (microprocessor
check, EPROM check, NOVRAM check)
DIP SWITCH
SW1 – 5:
Address (0 to 31)
SW6 – 12:
Function Selection
AGENCY APPROVALS
FCC Part 15
UL916 Energy Management Equipment
UL94-V0 Plenum Rated Enclosure
MICROREGULATOR INTERFACE
(MRI)
AVAILABLE PLATFORMS:
7792 MRI
7793 MCI
7798 I/SITE LAN
COMMUNICATION PORTS
MICROREGULATOR LAN:
RS-485, 9600 baud, asynchronous, polling
NETWORK WIRING REQUIREMENTS
MR LAN LENGTH:
5000 ft (1500 m)
CABLE SUPPORTED
Twisted pair, shielded. 24 AWG or larger, 30
pF/ft or less between conductors, 55 pF/ft
or less conductor to shield, 85 to 150 Ohm
impedance. Belden 9841 or equivalent.
PROCESSOR
PROCESSOR:
Zilog 86193
MEMORY
EPROM:
32KBytes
RAM:
464Bytes
NOVRAM:
4096Bytes.
PHYSICAL DECRIPTION
BASEPLATE AND COVER DIMENSIONS:
8.0˝ L x 4.3˝ W x 2.4˝ H
(196 mm x 105 mm x 61 mm).
DIN RAIL MOUNTING ON BASE ENCLO-
SURE:
PC/ABS plastic rated UL94-VO
POWER REQUIREMENTS:
24Vac, +10%, 50/60 Hz
(8VA, plus triac load, 4 amp fused)
OPERATING TEMPERATURE:
32°F to 122°F (0°C to 50°C)
OPERATING HUMIDITY:
10 – 90% RH, non-condensing
All brand names, trademarks and registered trademarks are the property of their respective owners. Information contained within this document is subject to change
without notice.
Schneider Electric One High Street, North Andover, MA 01845 USA Telephone: +1 978 975 9600 Fax: +1 978 975 9674 www.schneider-electric.com/buildings
SDS-INET-VAV-X1-X2-A4.BU.N.EN.5.2006.0.00.CC
May 2006 gg
946676750.137.png
Zgłoś jeśli naruszono regulamin