Exercise 5.
1/. What requirement covers the level of voltage drop allowed on an installation?
2/. A 3.6kW heater is fed from a 230V supply via PVC/PVC multi-core cable
buried in the fabric of the building. It is run with one other circuit and is
protected via BS1361 cartridge fuse. The length of run is 15m and there is no
problem with the ambient temperature. What size of cable is necessary?
3/. A 5kW single-phase motor is fed from a 230V supply 20m away. It is
protected via HRC fuses and is wired in SWA multi-core cable clipped to
cable tray. It is run with two other circuits in an area that has an ambient
temperature of 40°C. What size of cable is required?
Answers to Exercise
1/. If the voltage dropped is greater than 4% of the supply voltage we really need
to look at increasing the size of the cable. For a 230V supply, a 4% volt drop
would be 9.2V.
The requirements of Regulation 525-01-01 are deemed to be satisfied
for a supply given in accordance with the Electricity Supply
Regulations 1988 as amended if the voltage drop between the origin
of the installation and a socket outlet or the terminals of the fixed
current using equipment does not exceed 4% of the nominal voltage
of the supply
This requirement requires us to consider the installation as a whole, from its’
beginning to the end of the installation, and not just on each individual circuit.
2/. Remember the diagram and the housekeeping.
Grouping
2 circuits; Table 4B1; Column 2; Enclosed Method 3 or 4 and Method 1; Cg=0.80
Ambient temperature
No factor applies
Installation Reference Method
Table 4A; No.2; Method 1
3 circuits; Table 4B1; Column 3; Single layer multicore on tray-touching; Cg=0.81
Table 4C1; Column 5; General purpose PVC; Ca=0.87
Table 4A; No.11; Method 11