EN_ACS50.pdf

(1627 KB) Pobierz
EN / ACS50 User's Guide
Drive IT
Low Voltage
Drives
User's Guide
for type ACS50
AC Drives
from 0.18 to 2.2 kW
40724150.025.png
ACS50 UserÓs Guides in other languages and ACS50 Technical Reference can be found
on the Internet: http://www.abb.com.
Enter ACS50 UG (or ACS50 TR ) into the search field. Click Search. Remove selection
Search Web pages (HTML) only and click Search.
3AFE68247756 REV E
EN
Effective: 20.10.2004
ABB Oy
AC Drives
P.O. Box 184
FI-00381 HELSINKI
FINLAND
Telephone +358 10 22 11
Fax
+358 10 22 22681
¨ 2004 ABB Oy. All Rights reserved.
Internet
http://www.abb.com
3
Safety instructions
About this manual
Read the following instructions carefully before proceeding with the
installation.
Warning! Dangerous voltage!
Only a competent electrician may install ACS50.
Never work on the drive, the motor cable or the motor when main
power is applied. After switching off the input power, always wait at
least for 5 minutes to let the intermediate circuit capacitors
discharge before you start working on the drive.
Note: DIP switches are at a dangerous voltage.
Note: Even when the motor is stopped, dangerous voltages are
present at power circuit terminals L/R, N/S, T1/U, T2/V and T3/W.
Note: Even when the unit is powered down, there may be
dangerous external voltages connected from outside to the relay
output terminals.
Warning! Hot surfaces!
During operation, the cooling element may reach high temperature
(>80 C). Make sure to follow the installation instructions.
This guide provides information necessary to install and start-up
the unit.
Delivery check
The delivery includes:
1. ACS50
2. UserÓs guide
3. Two clamps for the control cable (EMC units
only).
Check the rating plate and ensure that the
delivered device corresponds to the order.
EMC filter: E = Built in, N = No
Max. continuous output current ( I 2 ):
01A4 = 1.4 A, 02A2 = 2.2 A, 04A3 = 4.3 A,
07A6 = 7.6 A, 09A8 = 9.8 A
Supply voltage ( U 1 ):
1 = 110È120 VAC +10%/-15%
2 = 200È240 VAC +10%/-15%
ACS50-01_-____-_
General safety instructions
ACS50 starts the motor automatically after a supply break if the
external start signal is on.
Never attempt to repair a broken unit. ACS50 is not a field
repairable unit. Contact the supplier for replacement.
Install ACS50 in a locked or tool-openable space.
Do not connect input power to the unit more than once every three
minutes.
Altering the DIP switches will affect the function and performance
of ACS50. Check that the changes will not cause any risk to
persons or property.
Serial number (S/N) is printed on the rating plate.
(Y = manufacturing year, WW = manufacturing week)
40724150.026.png 40724150.027.png 40724150.028.png 40724150.001.png 40724150.002.png 40724150.003.png 40724150.004.png 40724150.005.png 40724150.006.png 40724150.007.png 40724150.008.png 40724150.009.png 40724150.010.png 40724150.011.png 40724150.012.png 40724150.013.png 40724150.014.png 40724150.015.png 40724150.016.png 40724150.017.png 40724150.018.png 40724150.019.png
4
Overview of the unit
ACS50 drive controls the speed of a 3-phase AC induction motor.
Input terminals, page 13
Protective earth (PE), page 13
Power on LED, page 17
DIP switches, page 10
Fault LED, page 17
Control potentiometers, page 12
Relay output terminals, page 14
Control cable terminals, page 14
Motor cable shield, page 13
Analogue input signal selector
(voltage/current), page 14
Motor cable terminals, page 13 . Sliding
cover provides additional insulation. Slide
the cover left to close.
Mounting clip, pages 8 - 9
Clamp plate, page 15 (EMC units only)
40724150.020.png 40724150.021.png 40724150.022.png
5
Installation and start-up steps
Read Safety instructions on page 3 before proceeding.
Action
Pg.
1
Check the delivery.
3
2
Ensure that the installation environment is suitable for ACS50.
6
3
Mount the unit.
8 - 9
4
Check applicability of the standard settings: Motor nominal frequency is 50 Hz; load is a pump or a fan; maximum output
frequency is 50 Hz. If the standard settings are not suitable, adjust the DIP switches.
10
5
Make sure the MOTOR I NOM potentiometer matches the rated current of the motor. It defines operation of the motor
thermal protection function.
12
6
Adjust the acceleration/deceleration time potentiometer ACC/DEC if necessary.
12
7
Connect the power supply cable and motor cables.
13
8
Connect the control wires.
14
9
Turn the power on. Green LED is illuminated. Note: Motor rotates if the start signal is active.
10 Set the speed reference and activate the start signal. The motor accelerates to the given speed reference.
16
40724150.023.png 40724150.024.png
Zgłoś jeśli naruszono regulamin